WirelessHART Fieldgate SWG70 7 Commissioning
Endress+Hauser 35
7.5 Create a FieldCare Project
Creating a FieldCare project will allow you to configure Fieldgate SWG70 and any HART device
(field device or adapter) in the wireless network via its DTM. The configuration of a field device can
be taken from the manufacturer’s operating manual, the configuration of the adapter is described in
Operating Instructions BA061S/04/en, SWA70 Wireless Adapter.
7.5.1 Add the HART IP CommDTM
The HART IP CommDTM is required for communication via Ethernet with FieldCare.
NOTE!
• If you wish to connect to FieldCare via the RS-485 interface, the HART Communication
CommDTM must be added and configured instead of the HART IP CommDTM.
• The procedure is similar to that described here, whereby the configuration involves other
parameters such as selection of multiplexer option, COM port and baudrate.
1 In the FieldCare project workspace, right-click on the Host node and select Add Device...:
2The Add New Device dialog opens:
Select HART IP Communication and press OK
The dialog closes and the HART IP Communication DTM is added below the Host node
3 If desired, the HART IP Communication DTM can be now configured offline
Right-click on the node and select Configuration.
The node name and timeout (default 10000 ms) can be changed
The changes are accepted when the Apply button is pressed.